Exact product identification
Your quotation references the complete manufacturer part number to keep the requested product clear.

TM221CE16U
A 16-point Ethernet controller with sinking NPN transistor outputs for negative-logic load circuits. It provides two fast outputs and uses 24 V DC controller power.
Warranty coverage and terms are confirmed with your order.
We coordinate the fastest available shipping option for your destination.
Available payment methods are handled through secure payment channels.
Carrier and delivery options are confirmed for your destination before dispatch.
Independent supplier: Xindustra is not an authorized distributor, reseller, or representative of Schneider Electric. Brand names are used for identification and compatibility purposes only. Read disclaimer
I/O, NPN output wiring, communication and installation details for TM221CE16U.
The NPN variant has nine digital inputs and seven sinking outputs. It is the negative-logic alternative to TM221CE16T, with a different load-current path rather than a different input count.
TM221CE16U
Schneider Electric
Modicon M221
Compact
16
Digital inputs plus digital outputs; analog inputs are additional
9
7
2 × 0–10 V DC
24 V DC
20.4–28.8 V DC operating range
Removable screw terminal blocks
The U suffix identifies sinking transistor outputs; T identifies sourcing transistor outputs and R identifies relay contacts. Output logic determines the load wiring, while the input circuits support sink/source sensor arrangements.
There are 9 digital inputs in total, not 9 regular inputs plus four more. Four of those channels—I0, I1, I6 and I7—can be assigned to high-speed counting at up to 100 kHz. The remaining 5 channels are regular digital inputs. Choose the configured counting mode and input filter for the actual signal.
24 V DC; IEC/EN 61131-2 Type 1; sink/source
19.2–28.8 V DC
I0, I1, I6, I7
Shielded; maximum 10 m
Unshielded; maximum 30 m
2 single-ended voltage inputs
0–10 V DC
10 bits
±1% of full scale
Not isolated from internal logic; negative poles connected internally
Dedicated supplied cables; 1 m
The two built-in analog channels accept 0–10 V voltage signals. Use an appropriate analog expansion module for current-loop measurement rather than treating the onboard connector as a native 4–20 mA input.
The NPN outputs sink current: connect the load toward the positive supply and use the negative-logic diagram. This is not a drop-in wiring exchange for the PNP controller. NPN outputs have no internal short-circuit protection; the original diagram shows protection on individual load branches as well as the supply.
NPN sinking transistor
7
0.5 A
24 V DC rated; 19.2–28.8 V DC range
3.5 A across Q0–Q6
Q0 and Q1; up to 100 kHz
Not built in
Up to 100 Hz with resistive loads
PLS / PWM / PTO / FREQGEN
The output-current budget is subject to the hardware guide’s ambient-temperature and output-voltage derating curves. Do not apply the highest operating temperature and full simultaneous-on loading as independent maxima. Fast output wiring must be shielded and no longer than 3 m.
TM221CE16U output wiring
M221 hardware guide EIO0000003313.04, page 174. Output supply terminals, load-current path and shielded wiring for Q0/Q1.
1 × RJ45; Modbus TCP/IP; 10/100 Mbit/s
1 × RJ45; RS-232 / RS-485
USB 2.0 Mini-B
SD card slot
Physical switch and configurable input control
| Parameter / condition | Connection / equipment | Supported configuration |
|---|---|---|
| Local I/O | TM3 or TM2 expansion bus | Up to 7 expansion modules |
| Remote I/O | TM3 transmitter / receiver pair | Up to 7 additional TM3 modules |
| Distributed I/O | TM3 bus coupler over the appropriate network | Separate bus-coupler configuration |
The permitted configuration also depends on expansion-bus power consumption. TM3 transmitter/receiver modules do not count toward the seven expansion-I/O-module limit.
This 16-point compact controller provides one cartridge slot for supported TMC2 options. A cartridge is optional, not part of the 9 digital-input / 7 output count. TM3 expansion modules and TMC2 cartridges are separate order items.
Use EcoStruxure Machine Expert – Basic for M221 application programming, hardware configuration and diagnostics. It is the Basic edition for this controller range, not the separate Machine Expert environment used for M241/M251 projects. USB Mini-B provides a local programming connection; this Ethernet model also has a network interface.
512 kbytes
256 kbytes
256 kbytes
256 kbytes
Configured in Machine Expert – Basic
| Parameter / condition | Horizontal mounting | Vertical mounting |
|---|---|---|
| Ambient operating temperature | −10 to +55 °C | −10 to +35 °C |
| Expansion-module position | Beside the controller | Above the controller |
IP20 with protective covers fitted
DIN rail or panel
−25 to +70 °C
10–95%; noncondensing
0–2000 m
Pollution degree 2; enclosed industrial cabinet
Install the controller in an enclosure and maintain the mounting clearances in the hardware guide. Route power wiring separately from analog, communication and fast-I/O cables; shield the latter and terminate their shields at the grounding arrangement. M221 is a standard logic controller, not a safety controller.
Manufacturer resources for controller selection, wiring and programming.
Order the exact product and condition your project requires, with assistance from quotation through delivery.
Your quotation references the complete manufacturer part number to keep the requested product clear.
Tell us whether you need new original, new surplus, used, refurbished or repaired equipment.
Shipping options are prepared around your destination, quantity and requested delivery date.
Access available manufacturer product data, manuals and certificates associated with the order number.