Schneider Electric Modicon M221 compact Relay Ethernet logic controller

Schneider Electric TM221CE16R Modicon M221 16-I/O Compact Relay Ethernet Controller

TM221CE16R

A compact Ethernet PLC for discrete machine sequencing with seven relay outputs. Its 100–240 V AC controller supply and isolated output commons suit a cabinet using separately powered AC or DC actuators.

Availability
In Stock
Available quantity
12 units
Condition
New Original
SKU
TM221CE16R
Lifecycle
Active
$359.00
Request a quote
Ask a product question

12 months warranty

Warranty coverage and terms are confirmed with your order.

Fast shipping

We coordinate the fastest available shipping option for your destination.

Secure payment

Available payment methods are handled through secure payment channels.

Worldwide delivery

Carrier and delivery options are confirmed for your destination before dispatch.

Independent supplier: Xindustra is not an authorized distributor, reseller, or representative of Schneider Electric. Brand names are used for identification and compatibility purposes only. Read disclaimer

Technical specifications

I/O, relay load circuits, communication and installation details for TM221CE16R.

16-point compact Ethernet controller

The 16-point compact controller has nine digital inputs and seven relay outputs. Choose it for modest hardwired I/O counts when relay contacts are preferable to a sourcing or sinking transistor output.

Controller configuration

Manufacturer part number

TM221CE16R

Brand

Schneider Electric

Product family

Modicon M221

Form factor

Compact

Digital I/O total

16

Digital inputs plus digital outputs; analog inputs are additional

Digital inputs

9

Digital outputs

7

Analog inputs

2 × 0–10 V DC

Controller supply

100–240 V AC

85–264 V AC operating range; 50/60 Hz rated

I/O connection

Removable screw terminal blocks

What distinguishes this model

The R suffix identifies relay contacts. This compact CE relay model has a 100–240 V AC controller supply; a 24 V DC transistor controller or Book relay controller is a different electrical selection.

Digital signals and counting

There are 9 digital inputs in total, not 9 regular inputs plus four more. Four of those channels—I0, I1, I6 and I7—can be assigned to high-speed counting at up to 100 kHz. The remaining 5 channels are regular digital inputs. Choose the configured counting mode and input filter for the actual signal.

Input characteristics

Digital input circuit

24 V DC; IEC/EN 61131-2 Type 1; sink/source

Digital input voltage range

19.2–28.8 V DC

Fast input channels

I0, I1, I6, I7

Fast input cable

Shielded; maximum 10 m

Regular input cable

Unshielded; maximum 30 m

Analog channels

2 single-ended voltage inputs

Analog range

0–10 V DC

Analog resolution

10 bits

Analog input accuracy

±1% of full scale

Analog isolation

Not isolated from internal logic; negative poles connected internally

Analog connection

Dedicated supplied cables; 1 m

Voltage inputs are not 4–20 mA inputs

The two built-in analog channels accept 0–10 V voltage signals. Use an appropriate analog expansion module for current-loop measurement rather than treating the onboard connector as a native 4–20 mA input.

Connect the correct load circuit

Relay contacts switch separately supplied AC or DC load circuits. The controller supply voltage is not the voltage delivered automatically at the output terminals. Protect each load branch and its common circuit; use a freewheeling diode for inductive DC loads or an RC snubber for inductive AC loads. Capacitive loads are not supported.

Output characteristics

Output circuit

Normally open relay contacts

Total digital outputs

7

Rated current per output

2 A

Output voltage

24 V DC or 240 V AC rated

Output current budget

7 A for Q0–Q3; 6 A for Q4–Q6

Fast outputs

Not provided

Short-circuit protection

Not built in

Maximum switching rate at maximum load

20 operations per minute

Switching time

10 ms maximum on / off

Relay loads and separate commons

Relay contact life depends on load type and switching power; the 2 A contact rating is not an inductive-load lifetime guarantee. The groups shown in the wiring diagram are separate commons.

Output connection diagram

TM221CE16R output wiring

M221 hardware guide EIO0000003313.04, page 166. Output commons, load-protection circuits and Type T fuse symbols.

TM221CE16R output wiring

Official TM221CE16R output wiring diagram with terminal labels and circuit legend

M221 hardware guide EIO0000003313.04, page 166. Output commons, load-protection circuits and Type T fuse symbols.

Two commons: COM0 and COM1

The terminal drawing labels COM0 for Q0–Q3 and COM1 for Q4–Q6. They are separate output groups, with 7 A and 6 A common-current limits respectively.

Built-in interfaces

Ethernet

1 × RJ45; Modbus TCP/IP; 10/100 Mbit/s

Serial line

1 × RJ45; RS-232 / RS-485

Programming port

USB 2.0 Mini-B

Removable storage

SD card slot

RUN/STOP

Physical switch and configurable input control

Expansion architectures

Expansion architectures
Parameter / conditionConnection / equipmentSupported configuration
Local I/OTM3 or TM2 expansion busUp to 7 expansion modules
Remote I/OTM3 transmitter / receiver pairUp to 7 additional TM3 modules
Distributed I/OTM3 bus coupler over the appropriate networkSeparate bus-coupler configuration

The permitted configuration also depends on expansion-bus power consumption. TM3 transmitter/receiver modules do not count toward the seven expansion-I/O-module limit.

Optional compact-controller cartridges

This 16-point compact controller provides one cartridge slot for supported TMC2 options. A cartridge is optional, not part of the 9 digital-input / 7 output count. TM3 expansion modules and TMC2 cartridges are separate order items.

Program with Machine Expert – Basic

Use EcoStruxure Machine Expert – Basic for M221 application programming, hardware configuration and diagnostics. It is the Basic edition for this controller range, not the separate Machine Expert environment used for M241/M251 projects. USB Mini-B provides a local programming connection; this Ethernet model also has a network interface.

Application and data memory

Total RAM

512 kbytes

Application and data RAM

256 kbytes

Internal-variable RAM

256 kbytes

Nonvolatile application/data backup

256 kbytes

I/O expansion setup

Configured in Machine Expert – Basic

Installation conditions

Installation conditions
Parameter / conditionHorizontal mountingVertical mounting
Ambient operating temperature−10 to +55 °C−10 to +35 °C
Expansion-module positionBeside the controllerAbove the controller

Cabinet and environment

Protection

IP20 with protective covers fitted

Mounting

DIN rail or panel

Storage temperature

−25 to +70 °C

Relative humidity

10–95%; noncondensing

Operating altitude

0–2000 m

Installation environment

Pollution degree 2; enclosed industrial cabinet

Leave room for wiring and ventilation

Install the controller in an enclosure and maintain the mounting clearances in the hardware guide. Route power wiring separately from analog, communication and fast-I/O cables; shield the latter and terminate their shields at the grounding arrangement. M221 is a standard logic controller, not a safety controller.

Sourcing and order support

Order the exact product and condition your project requires, with assistance from quotation through delivery.

Exact product identification

Your quotation references the complete manufacturer part number to keep the requested product clear.

Condition options

Tell us whether you need new original, new surplus, used, refurbished or repaired equipment.

International delivery

Shipping options are prepared around your destination, quantity and requested delivery date.

Documentation support

Access available manufacturer product data, manuals and certificates associated with the order number.