S8VK-G06024
S8VK-G 60 W-class DIN rail power supply with 24 V DC, 2.5 A rated output. Single-phase 100–240 V AC nominal input, screw terminals and 3 A temporary power boost under the specified duty conditions.
Warranty coverage and terms are confirmed with your order.
We coordinate the fastest available shipping option for your destination.
Available payment methods are handled through secure payment channels.
Carrier and delivery options are confirmed for your destination before dispatch.
Independent supplier: Xindustra is not an authorized distributor, reseller, or representative of Omron. Brand names are used for identification and compatibility purposes only. Read disclaimer
Power, load and installation data for S8VK-G06024.
S8VK-G06024
60 W
24 V DC
2.5 A
3 A
Single-phase100–240 V AC
85–264 V AC
88% typical at230 V AC, rated output/load
−10% to+15% with V.ADJ, guaranteed range
Green DC ON LED
Set the output for the connected24 V loads and measure the actual voltage after adjustment. Increasing voltage does not increase the permitted output power or current. Do not supply this unit from an inverter output.
Overload protection automatically clears when current returns within the rated range. Overvoltage protection shuts off the output at approximately130% or more of nominal voltage; remove the cause, switch input power off for at least three minutes, then reapply power.
The 3 A boost value supports temporary demand above the 2.5 A rated current. Each boost interval must be10 seconds or less, boost duty30% or less, and average current over the full cycle no higher than the rated current. Ambient temperature and mounting orientation also limit the available load.
Data sheet p.11. Select the 60 W curve and mounting orientation. Below90 V AC, additional input-voltage derating applies.
The specified ambient range is−40 to+70 °C with temperature-dependent derating, no condensation or icing. At−40 to−25 °C, startup takes longer and ripple can exceed the normal table value. Full rated load is not available at every temperature or orientation.
Up to two units of the same model can operate in parallel at−25 to+40 °C. Adjust output voltage difference to50 mV or less, use matched lead length and thickness, and establish balanced output currents. There is no automatic current-balancing function; rapidly changing loads may require the specified redundancy unit or diode arrangement. Series operation also requires the manufacturer’s external diode circuit.
32 ×90 ×110 mm
DIN rail, standard vertical orientation
Screw
Natural convection; no cooling fan
IP20
8–10 mm
Data sheet p.14. Use the 60 W drawing; dimensions include the manufacturer’s stated projections/tolerances.
Data sheet p.20. Select the exact S8VK-G06024 row and input/output/PE column; wire sizes differ by power class.
Keep at least30 mm clearance above and below for convection and20 mm around the indicated neighboring surfaces. Connect PE and route input and output to their marked terminals. Standard vertical mounting provides the primary rating; horizontal mounting needs the appropriate bracket and derating. Side mounting is supported only for15 W models with the specified bracket.
Order the exact product and condition your project requires, with assistance from quotation through delivery.
Your quotation references the complete manufacturer part number to keep the requested product clear.
Tell us whether you need new original, new surplus, used, refurbished or repaired equipment.
Shipping options are prepared around your destination, quantity and requested delivery date.
Access available manufacturer product data, manuals and certificates associated with the order number.