S8VK-G 15 W-class DIN rail power supply with 24 V DC, 0.65 A rated output. Single-phase 100–240 V AC nominal input, screw terminals and 0.78 A temporary power boost under the specified duty conditions.

Availability
In Stock
Condition
New Original
SKU
S8VK-G01524
Lifecycle
Active

12 months warranty

Warranty coverage and terms are confirmed with your order.

Fast shipping

We coordinate the fastest available shipping option for your destination.

Secure payment

Available payment methods are handled through secure payment channels.

Worldwide delivery

Carrier and delivery options are confirmed for your destination before dispatch.

Independent supplier: Xindustra is not an authorized distributor, reseller, or representative of Omron. Brand names are used for identification and compatibility purposes only. Read disclaimer

Technical specifications

Power, load and installation data for S8VK-G01524.

Power conversion

Manufacturer part number

S8VK-G01524

Power class

15 W

Rated output

24 V DC

Rated output current

0.65 A

Temporary boost current

0.78 A

Nominal AC supply

Single-phase100–240 V AC

Allowable AC input

85–264 V AC

Efficiency

80% typical at230 V AC, rated output/load

Output adjustment

−10% to+15% with V.ADJ, guaranteed range

Output indicator

Green DC ON LED

Keep voltage, current and power within rating

Set the output for the connected24 V loads and measure the actual voltage after adjustment. Increasing voltage does not increase the permitted output power or current. Do not supply this unit from an inverter output.

Overload and overvoltage act differently

Overload protection automatically clears when current returns within the rated range. Overvoltage protection shuts off the output at approximately130% or more of nominal voltage; remove the cause, switch input power off for at least three minutes, then reapply power.

Temporary120% current is a duty-limited capability

The 0.78 A boost value supports temporary demand above the 0.65 A rated current. Each boost interval must be10 seconds or less, boost duty30% or less, and average current over the full cycle no higher than the rated current. Ambient temperature and mounting orientation also limit the available load.

Manufacturer load derating by temperature and mounting

Data sheet p.11. Select the 15 W curve and mounting orientation. Below90 V AC, additional input-voltage derating applies.

Manufacturer load derating by temperature and mounting

Manufacturer load derating by temperature and mounting

Data sheet p.11. Select the 15 W curve and mounting orientation. Below90 V AC, additional input-voltage derating applies.

Use the applicable curve across the ambient range

The specified ambient range is−40 to+70 °C with temperature-dependent derating, no condensation or icing. At−40 to−25 °C, startup takes longer and ripple can exceed the normal table value. Full rated load is not available at every temperature or orientation.

Parallel operation requires manual balancing

Up to two units of the same model can operate in parallel at−25 to+40 °C. Adjust output voltage difference to50 mV or less, use matched lead length and thickness, and establish balanced output currents. There is no automatic current-balancing function; rapidly changing loads may require the specified redundancy unit or diode arrangement. Series operation also requires the manufacturer’s external diode circuit.

Installed unit

Width ×height ×depth

22.5 ×90 ×90 mm

Mounting

DIN rail, standard vertical orientation

Terminals

Screw

Cooling

Natural convection; no cooling fan

Protection degree

IP20

Wire stripping length

8–10 mm

Manufacturer outline dimensions

Data sheet p.14. Use the 15 W drawing; dimensions include the manufacturer’s stated projections/tolerances.

Manufacturer outline dimensions

Manufacturer outline dimensions

Data sheet p.14. Use the 15 W drawing; dimensions include the manufacturer’s stated projections/tolerances.

Manufacturer conductor sizing table

Data sheet p.20. Select the exact S8VK-G01524 row and input/output/PE column; wire sizes differ by power class.

Manufacturer conductor sizing table

Manufacturer conductor sizing table

Data sheet p.20. Select the exact S8VK-G01524 row and input/output/PE column; wire sizes differ by power class.

Preserve convection and protective earthing

Keep at least30 mm clearance above and below for convection and20 mm around the indicated neighboring surfaces. Connect PE and route input and output to their marked terminals. Standard vertical mounting provides the primary rating; horizontal mounting needs the appropriate bracket and derating. Side mounting is supported only for15 W models with the specified bracket.

Sourcing and order support

Order the exact product and condition your project requires, with assistance from quotation through delivery.

Exact product identification

Your quotation references the complete manufacturer part number to keep the requested product clear.

Condition options

Tell us whether you need new original, new surplus, used, refurbished or repaired equipment.

International delivery

Shipping options are prepared around your destination, quantity and requested delivery date.

Documentation support

Access available manufacturer product data, manuals and certificates associated with the order number.