Skip to content
Honeywell XNX transmitter with local MPD sensor assembly

Honeywell XNX-AMSV-NNCB1 XNX mV / MPD Catalytic Transmitter

XNX-AMSV-NNCB1

ATEX/IEC XNX mV transmitter, 316 stainless steel, M25 entries, 16–32 V DC. Includes MPD catalytic sensor, 0–100% LEL. 4–20 mA with HART.

Availability
In Stock
Available quantity
12 units
Condition
New Original
SKU
XNX-AMSV-NNCB1
Lifecycle
Active
$2,945.00
Request a quote
Ask a product question

12 months warranty

Warranty coverage and terms are confirmed with your order.

Fast shipping

We coordinate the fastest available shipping option for your destination.

Secure payment

Available payment methods are handled through secure payment channels.

Worldwide delivery

Carrier and delivery options are confirmed for your destination before dispatch.

Independent supplier: Xindustra is not an authorized distributor, reseller, or representative of Honeywell. Brand names are used for identification and compatibility purposes only. Read disclaimer

Technical specifications

Configuration, sensor-system integration and installation data for XNX-AMSV-NNCB1.

316 SS, ATEX/IEC, M25

XNX-AMSV-NNCB1 is a complete configured Honeywell XNX transmitter order code: 316 stainless steel housing, ATEX/IEC approval selection, M25 entries and mV input with MPD catalytic sensor. The standard 4–20 mA/HART configuration has no optional output module or local HART port.

Exact order-code interpretation

Manufacturer part number

XNX-AMSV-NNCB1

Approval

ATEX/IEC

Entry thread

M25

Housing

316 stainless steel

Sensor personality

mV

Output option

N — no optional output module

Local HART port

N — not fitted

Sensor / range suffix

CB1 — MPD catalytic, 0–100% LEL

Use the full code for a replacement

M25 threads, ATEX/IEC approval selection and the mV input personality are part of this product’s identity. The 316 stainless steel housing is approximately 5 kg before separately selected sensing equipment. A different personality, entry thread or fitted option changes the ordered configuration.

A configured flammable-gas detector assembly

XNX-AMSV-NNCB1 combines an XNX mV-personality transmitter with an MPD catalytic-bead sensor for 0–100% LEL flammable-gas detection. CB1 identifies the supplied catalytic sensor; it is not an infrared, toxic-gas or oxygen cartridge.

Supplied MPD catalytic sensing

Sensor configuration

MPD with CB1 catalytic-bead cartridge

Measurement

Flammable gas concentration

Default full-scale range

0–100% LEL

Selectable full-scale span

20–100% LEL

10% LEL steps in the manufacturer MPD table.

Primary calibration gas

Methane

Default calibration point

50% LEL

Maximum system power

6.5 W

Documented XNX mV with catalytic/IR cell assembly.

Catalytic sensing and infrared sensing are different choices

The supplied catalytic sensor measures flammable gases using the catalytic-bead principle. Calibration gas and target-gas response belong to the sensing setup; a %LEL value is not a toxic-gas ppm or oxygen-volume measurement. This CB1 assembly is not the MPD infrared IF1, IV1 or IC1 configuration.

The sensor is part of this order code

Unlike an XNX code ending NNN, this NNCB1 configuration includes the specified MPD catalytic sensing assembly. The first two N characters mean no optional output module and no local HART port; they do not remove the standard HART-over-current-loop output.

Electrical integration

Nominal supply

24 V DC

Permissible terminal supply

16–32 V DC

Standard signal output

4–20 mA with HART

Current-loop topology

Selectable source, sink or isolated mode

Signal accuracy

±1% of full scale

Current output accuracy, not gas-sensor measurement accuracy.

Terminal conductors

0.5–2.5 mm²

Cage-style plug-in terminals with retaining screws.

Local controls

Magnetic switches; multilingual backlit LCD

Status indication

Alarm, power and fault LEDs

Supply voltage is required at the transmitter

Account for the connected detector, cable resistance and controller input when choosing the supply and cable. Source/sink/isolated switches are on the rear of the POD; the wiring and current-loop load must match the selected arrangement.

No optional output module is installed

The N option code supplies standard 4–20 mA with HART, without relay, Modbus RTU or FOUNDATION Fieldbus output hardware. Those are other module configurations, not simultaneously available outputs of this exact order code.

HART on the loop; no separate local port

HART communication is available over the standard 4–20 mA signal. The local-HART code is N, so this unit does not include the optional externally accessible HART connection port.

Housing and mounting

Enclosure material

316 stainless steel

Housing finish

Marine-grade coating

Approximate transmitter mass

5 kg

Transmitter housing reference; not a packed shipping weight or a complete remote detector system.

Housing entry paths

Five M25 entries

Sensor or local-HART hardware occupies an entry when fitted.

Mounting

Integral surface-mount lugs

Other mounting arrangements

Pipe or ceiling mounting with separately selected brackets

Enclosure protection

IP66 / NEMA 4X

Transmitter temperature range

−40 to +65 °C

The selected sensor/detector can impose a narrower operating range.

Original MPD assembly outline

Manufacturer drawing for XNX with MPD sensor, in millimetres. Aluminum outline is shown; the manufacturer notes small stainless-steel body differences with unchanged mounting-hole locations. Applies to the local MPD assembly layout, not a sensorless or remote-detector envelope.

Original MPD assembly outline

Honeywell original XNX with MPD front and side dimensional drawing including mounting-hole pitch and sensor clearance

Manufacturer drawing for XNX with MPD sensor, in millimetres. Aluminum outline is shown; the manufacturer notes small stainless-steel body differences with unchanged mounting-hole locations. Applies to the local MPD assembly layout, not a sensorless or remote-detector envelope.

Reserve space below the MPD

The sensor occupies the lower housing entry and extends below the transmitter body. Keep access to the sensing inlet and calibration connection; the transmitter-body dimensions alone do not describe the installed assembly.

Original transmitter construction

Manufacturer platform construction diagram. The EC barrier is a different personality’s component, not part of this mV input specification. The optional local HART interface shown is not fitted on this N-code model.

Original transmitter construction

Original Honeywell XNX construction diagram identifying the cover, POD, enclosure, mounting lugs and optional interfaces

Manufacturer platform construction diagram. The EC barrier is a different personality’s component, not part of this mV input specification. The optional local HART interface shown is not fitted on this N-code model.

Keep thread and approval selections together

XNX-AMSV-NNCB1 uses M25 entries under its ATEX/IEC ordering selection. Use the corresponding certified glands/conduit and stopping plugs. The five housing entries are not five unused cable ports once a sensor or local interface has been fitted.

Sourcing and order support

Order the exact product and condition your project requires, with assistance from quotation through delivery.

Exact product identification

Your quotation references the complete manufacturer part number to keep the requested product clear.

Condition options

Tell us whether you need new original, new surplus, used, refurbished or repaired equipment.

International delivery

Shipping options are prepared around your destination, quantity and requested delivery date.

Documentation support

Access available manufacturer product data, manuals and certificates associated with the order number.