Skip to content
ABB S200 trip curves and coordination guide with B, C and D magnetic operating bands

ABB S200 MCB trip curves, selectivity and back-up protection

B, C and D curves define different instantaneous magnetic trip bands; they do not, by themselves, prove that a breaker suits a load or coordinates with another device. This guide shows how to read the curves and verify an ABB S200 application.

Xindustra Editorial Team
Published November 2, 2025
Reviewed September 16, 2026
11 min read

Key takeaways

  • B, C and D mainly identify the instantaneous magnetic trip band: 3–5, 5–10 and 10–20 times rated current under IEC/EN 60898-1.
  • A higher curve letter can tolerate more inrush, but it also requires more fault current to operate magnetically and may affect disconnection-time compliance.
  • Breaking capacity is checked against the maximum prospective short-circuit current at the installation point; it is separate from the trip curve.
  • Selectivity and back-up protection describe different outcomes and must be verified for the exact upstream/downstream device pair, voltage and fault-current level.
  • ABB coordination tables or software—not a generic curve sketch—are the final authority in the instantaneous short-circuit region.

For ABB System pro M compact S200 miniature circuit breakers, the B, C or D marking primarily tells you where the electromagnetic release is expected to operate during a high overcurrent. It does not tell you the breaker’s interrupting rating, guarantee discrimination with an upstream device, or replace a short-circuit and disconnection-time calculation.

What an MCB trip curve actually shows

An MCB normally combines two release mechanisms. The thermal release responds to sustained overloads and operates on an inverse-time basis: more current generally means a shorter trip time. The electromagnetic release responds much faster to high overcurrent, such as a short circuit. The B, C and D designation changes the magnetic operating band; it is not a different continuous-current rating.

B, C and D instantaneous trip bands

Comparison of IEC/EN 60898-1 magnetic operating bands: B above 3 to 5 times rated current, C above 5 to 10 times, and D above 10 to 20 times, with corresponding current ranges for a 16 amp breaker
The magnetic release changes across B, C and D; the colored areas are tolerance bands, not single pickup values.

IEC/EN 60898-1 magnetic release comparison

CurveMagnetic operating bandWhat the band meansSelection implication
BAbove 3 × In to 5 × InLower instantaneous threshold of the threeMore sensitive to short-duration inrush; lower fault current is needed to enter the magnetic region
CAbove 5 × In to 10 × InIntermediate instantaneous thresholdAllows more inrush than B, but needs a higher fault current for magnetic operation
DAbove 10 × In to 20 × InHighest instantaneous threshold of the threeCan ride through larger inrush, but the protection calculation must support the higher threshold

The band is a tolerance zone, not one exact pickup value. Below the lower boundary, the magnetic release must not operate under the stated test condition; at the upper boundary, it must operate within the standard’s specified time. Between those boundaries, either behavior can be compliant. That is why a single line at 5, 10 or 20 times rated current is not an adequate model of a real breaker.

Worked example: a 16 A breaker

Multiplying the rated current In by the curve limits gives the magnetic band. For a 16 A device, B spans 48–80 A, C spans 80–160 A and D spans 160–320 A. These figures do not mean the breaker will always trip at the first number or wait until the second. They define the region in which the magnetic release transitions from required non-operation to required operation.

Magnetic bands for a 16 A MCB

CurveLower boundaryUpper boundary
B163 × 16 A = 48 A5 × 16 A = 80 A
C165 × 16 A = 80 A10 × 16 A = 160 A
D1610 × 16 A = 160 A20 × 16 A = 320 A

How to choose the curve without creating a protection problem

The practical objective is to let expected starting or energization current pass without nuisance tripping while still clearing the lowest credible fault current within the required time. Moving from B to C or D may solve one side of that equation and make the other side worse.

Check inrush as both current and time

A motor start, transformer energization, capacitor charging pulse and LED-driver inrush can reach similar peak currents but last for very different periods. Plot the manufacturer’s worst-case inrush envelope against the breaker’s upper trip boundary at the relevant ambient and installation condition. A peak multiplier with no duration is not enough to judge compatibility.

Check the minimum fault current and disconnection time

The far end of a long or high-impedance circuit may produce much less fault current than the supply end. If that minimum value does not reach the magnetic operating region, clearing depends on the slower thermal part of the curve. The design must still meet the applicable shock-protection and conductor-protection disconnection requirements. Increasing the curve from C to D without repeating this calculation can turn nuisance-trip relief into delayed fault clearance.

Apply the actual installation conditions

Thermal behavior is influenced by ambient temperature, adjacent loaded devices, enclosure conditions and conductor termination. The reference curve is a laboratory characteristic, not a guarantee that every installation behaves identically. Apply ABB’s correction or application guidance where the installation differs from the reference conditions.

Trip curve is not breaking capacity

The trip curve describes when the release commands an opening operation. Breaking capacity describes the short-circuit level the device is rated to interrupt under a stated standard, voltage and test sequence. A C-curve device is not inherently able to interrupt more fault current than a B-curve device.

Keep these short-circuit terms separate

TermWhat it describesHow it is used
Prospective short-circuit currentThe fault current that could flow at a point in the installation before a protective device limits itCalculate or measure it at the installation point; compare the maximum value with the applicable device or combination rating
IcnRated short-circuit capacity used for household and similar MCB applications under IEC/EN 60898-1Use the value marked or documented for the relevant voltage and pole arrangement
IcuRated ultimate short-circuit breaking capacity under IEC/EN 60947-2Shows the maximum tested breaking duty under that standard; it is not interchangeable with Icn
IcsRated service short-circuit breaking capacity under IEC/EN 60947-2Indicates the defined service-performance level after the specified short-circuit test sequence

Use the rating that belongs to the exact device, approval, voltage, frequency and pole configuration. If the maximum prospective short-circuit current exceeds the breaker’s applicable standalone capacity, the answer is not to choose a different trip curve. The design needs a device with sufficient capacity or an ABB-approved back-up combination.

What selectivity means between two breakers

Two protective devices in series are selective when an overcurrent on the load side causes the downstream device to open while the upstream device remains closed. The aim is continuity: only the affected branch is disconnected.

Total and partial selectivity

ResultMeaningEvidence required
Total selectivityThe downstream device alone clears overcurrents up to the stated limit of the combinationManufacturer data for the exact pair and stated electrical conditions
Partial selectivitySelectivity is assured only up to a stated limit current IsConfirm that the maximum prospective short-circuit current at the downstream location does not exceed Is
Not demonstratedBoth devices may operate for some faults, even if their rated currents differDo not infer selectivity from brand, frame size or curve letter

Time-current comparison works best in the overload region

For overload coordination, compare the downstream device’s maximum operating-time curve with the upstream device’s minimum non-operating or operating boundary, including tolerances. The curves need adequate separation across the current range being assessed. Comparing two nominal center lines can overstate the available margin.

The short-circuit region needs manufacturer coordination data

At high fault currents, current limitation, contact motion, arc voltage and let-through energy affect both devices before a simple time-current plot can describe the interaction. ABB states that selectivity limits in the instantaneous region are specific to the device combination and are obtained from test data. Use ABB’s selectivity tables, SOC or the current ABB coordination tool for the exact pair.

Back-up protection is useful—but it is not selectivity

Back-up protection, also called cascading, is a tested coordination in which an upstream current-limiting device reduces the short-circuit stress seen by a downstream device. This can allow the combination to be used at a prospective fault level above the downstream breaker’s standalone breaking capacity, but only up to the value stated by the manufacturer.

The desired outcome is different from selectivity. A selective combination aims to keep the upstream device closed. A back-up combination aims to interrupt the fault safely; operation of the upstream device may be part of that result. One ABB table may show a selectivity limit and a separate back-up value for the same pair. Neither value should be substituted for the other.

Comparison showing a downstream fault opening only the downstream breaker under selectivity, while an upstream current-limiting breaker may also operate when providing back-up protection
Selectivity protects continuity of supply; back-up coordination increases safe interrupting capability for a tested device combination.

A defensible ABB S200 selection workflow

Document the decision in this order

  1. 01

    Identify every device exactly

    Record the full ABB order code, number of poles, rated current, curve, applicable standard, rated voltage and breaking-capacity marking. Do the same for the upstream protective device.

  2. 02

    Define normal load and inrush

    Use measured data or the equipment manufacturer’s maximum starting or energization current and duration. Include operating cycles and simultaneous starts where relevant.

  3. 03

    Calculate both fault-current extremes

    Determine the minimum fault current used for disconnection-time verification and the maximum prospective short-circuit current used for interrupting-capacity and coordination checks.

  4. 04

    Check the complete time-current curve

    Verify that expected inrush remains below the breaker’s operating boundary while the minimum fault current produces acceptable clearing. Include tolerances and installation corrections.

  5. 05

    Verify short-circuit capacity

    Confirm that the applicable Icn, Icu or approved back-up rating is sufficient at the stated voltage. Do not mix values from different standards or product variants.

  6. 06

    Verify the exact upstream/downstream pair

    Use current ABB selectivity and back-up tables or software. Record whether selectivity is total or partial, the limit current Is, the back-up value and all conditions attached to the table.

  7. 07

    Retain the calculation and source revision

    Keep the device codes, fault-current assumptions, curve or table reference and document revision with the panel schedule. This makes later substitutions reviewable.

Common mistakes to avoid

Choosing D curve only to stop nuisance trips. This may mask an undersized circuit, an abnormal start, an incorrect breaker rating or a fault-current problem. Diagnose the event and repeat the protection checks before changing the curve.

Assuming different current ratings guarantee selectivity. Two devices can have separated overload curves and still operate together during a high-current fault. Check the exact combination table.

Comparing Icn directly with Icu or Ics. They belong to different standards and test duties. Use the value applicable to the installation and the marking on the selected product.

Treating back-up protection as permission to use any lower-rated downstream breaker. Cascading applies only to the tested combination, conditions and maximum value published by the manufacturer.

Replacing an S200-family device by visible dimensions alone. Similar front profiles can hide different standards, curves, capacities, terminal arrangements and accessories. Preserve the complete order code and coordination evidence.

Bottom line

Start with the B, C or D curve only after the load and its inrush are known. Finish the design only after minimum fault current, disconnection time, maximum prospective short-circuit current, breaking capacity and the exact ABB coordination data have all been checked. The curve letter is one input to that process—not the conclusion.

Frequently asked questions

Concise answers to common questions about the subject covered in this guide.

What is the practical difference between ABB B, C and D trip curves?

For IEC/EN 60898-1 B, C and D characteristics, the main difference is the magnetic instantaneous operating band: B is above 3–5 times In, C is above 5–10 times In and D is above 10–20 times In. A higher band tolerates more inrush but requires a higher fault current to ensure magnetic operation.

Should every motor circuit use a D-curve MCB?

No. Motor starting current and duration vary, and a D curve may make fault clearance harder on a high-impedance circuit. Compare the actual start envelope with the breaker curve and verify conductor protection, minimum fault current and the required disconnection time.

Does a D-curve breaker have a higher breaking capacity than a C-curve breaker?

Not because it is D curve. The curve identifies the release characteristic; breaking capacity is a separate rating stated for the exact device, standard, voltage and pole arrangement.

Are two ABB breakers automatically selective because they are from the same manufacturer?

No. Selectivity depends on the exact upstream and downstream devices and the fault-current level. Use ABB’s current coordination table or software to verify whether the pair has total selectivity, partial selectivity up to Is, or no published selectivity result.

What is the difference between selectivity and cascading?

Selectivity aims for only the downstream protective device to open so unaffected circuits remain energized. Cascading or back-up protection uses an upstream current-limiting device to help the downstream device interrupt a larger fault safely; the upstream device may also operate.

At what current does an ABB C16 MCB trip instantaneously?

Under the IEC/EN 60898-1 C characteristic, the magnetic band for a 16 A device is 80–160 A. It is a tolerance band, not one exact pickup point. Below, within and above the band, the standard specifies different required behavior and times; use the product’s full curve for design.

Need help identifying an ABB S200 replacement?

Send the complete order code, device markings, panel voltage and application details. We can review the identity and available sourcing options; protection design and approval remain with the qualified system designer.

Request a quote